FD30 vs FD60: what fire door ratings mean

Published · Updated · 7 min read

Cedric LaubscherFire Risk Assessor, Fyrup

FD30 is a doorset tested to 30 minutes of fire resistance. FD60 is the same idea for 60 minutes. The number is the only difference in the name. An "S" suffix (FD30S, FD60S) means the doorset also restricts cold smoke, which needs smoke seals and tighter gaps. The rating is proven in a furnace test to BS 476-22 or BS EN 1634-1, and on site you read it from a certification label, plug or data plate. You do not set fire to the door to check it.

FD30 vs FD60

FD30 and FD60 are the same kind of rating. FD30 means 30 minutes of fire resistance under a standard test. FD60 means 60 minutes. FD90 and FD120 exist for locations that need longer, and they are much less common. Nothing else about the letters changes: a higher number is not a different product family, and it is not a better door in a location that only needs 30 minutes.

The rating belongs to the doorset as installed — leaf, frame, seals, glazing and ironmongery together — not to the leaf alone. A correctly rated leaf hung in the wrong frame, or with the wrong hinges, may achieve nothing like its nominal rating. Which number a location needs comes from the fire strategy and from Approved Document B or BS 9999, not from the door.

What the numbers mean

FD30 and FD60 cover the vast majority of doors in commercial and residential buildings. FD90 and FD120 appear where compartmentation demands more — high-hazard rooms, some protected shafts, and buildings with extended evacuation strategies.

The S suffix: smoke as well as fire

Fire resistance and smoke control are different jobs. Intumescent seals expand in heat to hold back fire but do nothing against cold smoke early in a fire — which is what actually threatens escape routes first. Doors designated FD30S or FD60S must also restrict smoke leakage, which in practice means combined intumescent-and-smoke seals (or separate brush/fin seals) and much tighter gap tolerances, particularly at the threshold. Locations protecting means of escape — stair doors, corridor doors, flat entrance doors — typically need the S designation.

How a rating is proven

Ratings come from fire resistance testing to BS 476-22:1987 or BS EN 1634-1, and reach site as third-party certification: a colour-coded plug or label on the top edge of the leaf (BWF-Certifire, Q-Mark and similar schemes) or a data plate identifying the manufacturer and rating. On older doors with no marking, an experienced inspector may judge a solid-construction door to be a "notional" FD30 — a professional judgement that should be recorded as such, with the door’s construction described.

On site, the inspector’s question is two-fold: what rating does this location require, and what rating does the installed doorset demonstrably provide? AssessHub’s fire door inspection software records both — the FD rating and whether the door is certificated, nominal, notional or uncertificated — alongside the eight-point condition check, so the report shows not just which doors are damaged but which are simply the wrong door for the job.

How a fire door is tested on site

The furnace test is how the rating was earned, once, by the manufacturer. It is not what an inspector does in a corridor. A fire door testing procedure on site checks that the installed doorset still matches that tested condition: certification is present, the leaf and frame are intact, the gaps are within tolerance, the seals are continuous, and the closer shuts the leaf onto the latch.

The step-by-step version, including the closer release and the gap gauge, is how to inspect a fire door. The measurements and the pass or fail go on the fire door inspection template.

Frequently asked questions

What is the difference between an FD30 and an FD60 fire door?

Thirty minutes of tested fire resistance against sixty. The doorset — leaf, frame, seals, glazing and ironmongery — is what carries the rating. A location that needs FD30 does not become safer because an FD60 leaf was fitted badly, and a location that needs FD60 is not met by an FD30 door in perfect condition.

Where are FD30 doors required?

Typical FD30 locations include doors onto protected corridors and stairways, flat entrance doors (usually FD30S), and doors to rooms opening onto escape routes. The requirement for any specific location comes from the building’s fire strategy and Approved Document B or BS 9999 guidance, not from the door itself.

Can I upgrade an existing door to a fire door?

Sometimes. Upgrade systems exist (intumescent papers, seals, replacement glazing), but the result is only as good as the evidence behind it — the whole doorset must be considered, and many upgrades are not certifiable. Replacement with a certified doorset is often the more defensible route for critical locations.

Is a fire door rating invalidated by damage?

Effectively yes. A rating assumes the doorset is in the tested condition — a damaged leaf, missing seal, over-planed edge or wrong hinges can reduce a nominal FD30 to little or nothing, which is why condition inspection matters as much as the label.