How to inspect a fire door: the testing procedure
Published · 8 min read
To test a fire door on site, identify the door and the rating the location needs, read any certification, then check the leaf, frame, hinges, seals, glazing and signage, measure the gaps, and release the closer so the leaf shuts onto the latch. You are not fire-testing the door. A failure needs a comment, a photograph and a remedial action, written against that door and no other.
A site test is not a fire test
A fire door’s rating was earned in a furnace, to BS 476-22 or BS EN 1634-1, on a complete doorset. An inspection does not repeat that. The fire door testing procedure on site checks whether the door in front of you is still the doorset that was certified, and whether it still closes. If you need the difference between a 30-minute and a 60-minute door, that is FD30 vs FD60.
Write it down door by door. The fire door inspection template is one sheet per door, with the rating, the checks and the remedial action. The reasoning behind each check is the fire door inspection checklist.
Before you open the door
Record the site, the building, the level, a door reference and where the door is, so the next survey can find the same leaf. Then decide two things that the condition checks cannot answer: the FD rating this location needs, and whether you can actually inspect the door. A locked plant room or a flat you could not get into is a recorded limitation, not a pass and not a blank line.
The sequence
Work in an order that does not make you open and shut the leaf for every line. Look and then measure:
- Certification — a plug, label or data plate, usually on the top edge of the leaf. No mark does not by itself fail an older solid door; record a notional judgement as a judgement.
- Leaf and frame — damage, warping, delamination, holes, and anything that has been cut in or changed since the door was hung.
- Hinges — usually three per leaf, fixed tight, screws present, no metal fatigue.
- Seals — intumescent seals continuous and not painted over; smoke seals as well where the door is meant to control cold smoke.
- Glazing — only fire-rated glass, with the beading and seals intact.
- Signage — the correct notice on the correct faces.
- Gaps — a gauge at the head and both stiles, then the threshold.
- Closer and latch — last, because this is the part where you operate the door.
The closer test and the gap gauge
Open the leaf and let it go. It has to close fully onto the latch from any angle, including from about 75mm open. A closer that stops short, or a latch that does not hold the leaf, fails the door even when everything else looks tidy. Modern closers are specified to BS EN 1154. A hold-open device is acceptable only if it releases on the alarm.
The gap between leaf and frame at the head and both sides is commonly 3mm, with 2–4mm accepted. The threshold is often up to 8mm where only fire resistance is required, and nearer 3mm where cold smoke sealing matters. Write the millimetres down. "Looks about right" is not a record.
What to write when it fails
A failed check needs three things or it will not survive a question later: what is wrong, a photograph, and the remedial action. A door that is the wrong rating for the location fails even in perfect condition. How often you come back is a separate question, covered in how often fire doors should be inspected.
Fire door inspection software keeps this as a register: the same checks, the photograph on the door it belongs to, and a pass or fail that comes from the checks rather than from a summary written afterwards.
Frequently asked questions
How do you test a fire door closer?
Open the leaf and release it, including from about 75mm. It should shut fully onto the latch by itself from any open position. If it stops short, slams, or the latch does not hold it, the closer or the latch has failed. A hold-open device is only acceptable if it lets go when the alarm operates.
What gap should I measure on a fire door?
At the head and both stiles, 3mm is the usual figure, and 2–4mm is generally accepted. Under the door, up to about 8mm can be acceptable for fire resistance alone. Where the door has to stop cold smoke, the threshold gap needs to be much smaller, or a drop seal needs to close it.
Is a fire door inspection the same as a fire test?
No. The fire test is a laboratory furnace test of a doorset, to BS 476-22 or BS EN 1634-1, and it is how the FD rating was established. An inspection checks the installed door: certification, condition, gaps, seals and whether it closes.
Survey the block, issue the register the same day
AssessHub runs these checks on a phone with no signal, attaches the photographs to the door as you take them, and assembles the register and remedial plan in one click.